Conductive
Point level detection
Triple rod probe 11363Z

Probe 11363Z ©Endress+Hauser

High resistant probes for corrosive liquids in plastic vessels

The triple rod probe 11363Z is a high resistant probe for applications requiring accurate point level detection or overfill prevention in plastic vessels or vessels made of non-conducting material. Three different limit points can be detected with one probe in vessels with electrically conducting walls.

  • Fordele

    • Reliable and safe measurement

    • Safe measurement even for applications in explosion-hazardous area

    • Variable process connections for various applications

  • Anvendelsesområde

    Two-point point level detection in plastic vessels and vessels made of non-conducting material. For applications in explosion-hazardous areas or as overfill prevention for water-polluting liquids.

    • Process connections: Threads and flanges

    • Measuring range...

Funktioner og specifikationer

Tilbage

Details

  • Measuring principle

    Conductive

  • Characteristic / Application

    Triple rod probe with high-class media contacting wetted parts

  • Supply / Communication

    Relay

  • Ambient temperature

    -20 °C ... 80 °C
    (-4 °F ... 176 °F)

  • Process temperature

    -40 °C ... 150 °C
    (-40 °F ... 302 °F)

  • Process pressure absolute / max. overpressure limit

    Vacuum ... 30 bar
    (Vacuum ... 435 psi)

  • Min. conductivity of medium

    20 µS/cm

  • Main wetted parts

    PTFE, PFA, 316 TI, Alloy B/C4, Titan, Tantal, Monel

  • Process connection

    G 1 1/2A
    NPT1 1/2"
    Flange DIN /ASME

  • Sensor length

    0.1m ... 4m
    (4" ... 157")

  • Communication

    Relay

  • Certificates / Approvals

    ATEX, NEPSI

  • Safety approvals

    Overfill prevention WHG

  • Components

    Transmitter: FTW325

  • Application limits

    Observe min. medium conductivity

Dokumenter / Vejledninger / Software

Tilbehør / Reservedele

Nr
Order code
Specification